Commercial (UL/CSA)

UL 2129

Additional Details

APPLIANCE WIRING MATERIAL
Style 2129 Multi-conductor cable using Extruded Non-integral Jacket.
Rating 60, 80, 90, or 105 deg C; 600 or 1000 Vac, Horizontal flame.
Conductor 28 AWG – 9 AWG solid or stranded round.
Insulation Extruded PVC, 30 mils min average, 27 mils minimum at any point or Labled or complying with Manufacturer’s AWM Procedure.
Assembly Two or more singles, twisted pairs or groups of twisted singles twisted together, or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
Shield Optional
Jacket Extruded PVC
Dia. of cable under jacket in inches of 0.700 or less* 30 mils min average 24 mils minimum at any point
0.701-1.000 dia 45 avg 36 min
1.001-1.500 dia 60 avg 48 min
1.501-4.500 dia 80 avg 64 min
*Major diameter if cable is flat or oval.
Standard Appliance Wiring Material UL 758.
Marking General.
Use Internal wiring.
UL and the UL Logo are trademarks of UL LLC © 2014


If you don’t find what you’re looking for please contact us. The cable designs in this listing represent our standard product line. If you require special modifications or unique designs, SCC can create special cables for the most demanding applications. For custom applications please contact us.